Seth was great. Very professional. diagnosed the problem quickly and set up the follow up repairs and parts for us.
Upon arrival inspected unit and found freezing temps inside. Inspected blower and blower motor will not change speed. Stuck in low speed. Blower motor will need replaced under parts warranty
Pulled and cleaned blower assembly with water and brush Brush cleaned and vacuumed secondary heat exchanger
Need two guys to pickup AC and pad to put a thicker base of gravel under. Will need to schedule a morning for this job.
Performed cooling maintenance on a Carrier AC system Washed aprilaire dehumidifier filter Humidifier shut down for summer Replaced 20x25x4 filter Left an additional filter per customer request at additional charge Blower is clean Drains are clear No concerns found on indoor portion of the system Tore down and washed outdoor unit **UNIT IS NOT PROPERLY GROUNDED** Builder needs to send their electrician out to correct this. Refrigerant charge is good Please pay balance for the extra filter. Thank you!
2022 Carrier AC is running in great condition. 20x25x4 air filter in good condition. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Run test unit in cooling mode from thermostat. Delta t of 21F with supply temp of 50F. Refrigerant pressures are within spec. High 275psi with 11F SC, low 115psi with 10F SH. Water flushed outdoor coils to remove dirt and debris. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer. Regarding concerns of temperature differences between floor levels, recommend closing register ins basement, partially closing som on the first floor in areas that are not used often, make sure all registers on second floorare open, and leaving fan setting on thermostat in ON mode to continuously run the fan. All of these combined will help lower the temperature difference, but it will not eliminate it.
2016 Carrier AC running in good condition. 20x25x1 air filter in decent condition. Check again soon. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Run test unit in cooling mode. Delta t of 19F with supply temp of 49F. Refrigerant pressures are within spec. High 275psi with 14F SC, low 115psi with 8F SH. Outdoor coils flushed with water to remove dirt and debris. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer.
2023 Carrier AC running in great condition. 20x25x4 air filter in good condition. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Run test unit in cooling mode from thermostat. Delta t of 22F with supply temp of 50F. Refrigerant pressures are within spec. High 320psi with 11F SC, low 120psi with 10F SH. Outdoor coils are in clean condition. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer. Inspection on basement fan was inconclusive as fan started operating after being removed and inspected, then reinstalled.
Performed cooling maintenance on two Carrier AC systems Filters are new Blowers are clean Shut down humidifier Checked dehumidifier Drains are clear Refrigerant charge is correct for both systems Capacitors are in specification Wiring is secure and free of damage Disassembled both outdoor units and washed them with water Advised leaving the fan set to continuous operation for the downstairs system in the summer time to enable the whole-house dehumidifier to work more effectively.
2022 Carrier AC running in new condition. 20x25x4 air filter is new today. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Confirm proper blower speeds for cooling more on furnace blower settings. Run test unit in cooling mode from thermostat. Delta t of 20F with supply temp of 48F. Refrigerant pressures are within spec. High 245psi with 11F SC, low 115psi with 9F SH. Outdoor coils are in clean condition. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer.
Perform heating PMI Clean flame sensor Flush drain trap Check blower and inducer amps verifying within spec Check delta T @ 55° Filter 24x25x4 due soon. No other concerns at this time only concerns discovered were drain trap and filter. Trap has been flushed and resolved
Performed furnace maintenance Pulled and cleaned thr flame sensor Checked Condensate drains Filter is not new but OK Burner manifold gas pressure set to 3.0" water column Temperature rise 49⁰ with the humidifier running Fixed a water leak on the humidifier supply line Humidifier water panel is in like-new condition Closed humidifier bypass damper to summer position Run tested AC Outdoor coil is OK Refrigerant charge is correct Temperature drop 18⁰ System is operating within factory specifications at this time.
Performed cooling maintenance on two Daikin Fit ACs and one Daikin minisplit heat pump Changed aprilaire 210 filters on both furnaces Blowers are clean Drains are clear No stored fault codes Checked furnaces for water leaks that may have developed over the heating season Aprilaire dehumidifier filter is OK Minisplit filters are OK Washed the outdoor coils Checked refrigerant charges All three systems are clean and running in factory specifications.
2019 Carrier AC running in great condition. 20x25x4 air filter in dirty condition. Recommend changing soon. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Run test unit in cooling mode from thermostat. Delta t of 20F with supply temp of 49F. Refrigerant pressures are within spec. High 235psi with 12F SC, low 110psi with 9F SH. Outdoor coils are in clean condition. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer.
No power to the outside unit Found breaker in the tripped off position that looked like it was in the on position. After turning off and back on the breaker reset normal and the system runs normal Cooling mode dropped to 50° supply temperature with 240 volts pulling 9 amps. Refrigerant suction pressure is normal at 112psi. 45/5 power supply is perfect and starting relay is like new All equipment is running in normal condition at this time Thermal scan of breaker box shows normal heat on the AC breaker after 10 minutes of running time Possible power surge or brown out causing the tripped breaker Recommend homeowners consult with electricians if problem persists. Eaton 40 amp 2 pole